There are 3 organizations, the National Electrical Safety Code, National Electric Code, and the State of Texas, that influence these general standards. When the standard varies, the strictest option is required. If code standards are in question, members are encouraged to contact their local code authority.

Vertical Clearance Requirements for Energized Lines from 0 to 750 volts*

LocationHeight
Railroads24 feet
Public streets, alleys, roads and highways22 feet
Commercial driveways, parking lots & other areas subject to truck traffic22 feet
Residential driveways16 feet
Other land with vehicle traffic16 feet
Spaces or ways with pedestrian traffic12 feet
Spaces with limited building height (300 volts or less)No less than 10.5 feet
Rural land beside roadway14 feet
Urban land beside roadway16 feet
Swimming areas22.5 feet
Building roofs (no pedestrians)3.5 feet
Building roofs (with pedestrians)11 feet
Signs, chimneys, antennas, tanks3.5 feet

*For clearance information on lines energized above 750 volts, contact BEC.