Standard Voltages and Guidelines
Bandera Electric follows the range of service voltages
in use by the American National Standards Institute (ANSI) for Electric Power
Systems and Equipment
C84.1-1989. The term "service voltage" is defined as the point where BEC's
electrical system connects with that of a member.
- Desirable -- requires that occurrences of service
voltages outside range are infrequent
- Acceptable -- are occurrences outside desirable
range resulting from practical design or operating conditions that are limited
in extent, frequency and duration
For more details about our service voltages
contact the cooperative.
|
ANSI Standard C84.1
|
| Nominal
Service Voltage |
Desirable
range |
Acceptable
Range |
| 120 |
126-114 |
127-110 |
| 208 |
218-197 |
220-191 |
| 240 |
252-228 |
254-220 |
| 277 |
291-263 |
293-254 |
| 480 |
504-456 |
508-440 |
|
Higher voltages (at primary level) are also part of
BEC's nominal service voltages.
Contact the cooperative for information about primary
level voltages. |
|